Modular Rigidwall Cleanrooms

LogiClean®: A Revolutionary Concept in Rigidwall Cleanroom Design

Technical Air Products’ LogiClean® rigidwall cleanrooms offer the same flexibility and performance as our softwall cleanrooms, but with a more robust and durable wall system.  Our proprietary LogiClean® design gives you the flexibility to quickly and easily turn any space into a high performance modular rigidwall cleanroom.  When your business grows, your LogiClean® cleanroom can grow with you.  Our modular design makes them easy to assemble or disassemble, and economical to add on to.  Our cleanrooms are completely self-supporting, requiring no complex ceiling supports.

Our Rigidwall cleanrooms are prefabricated, free standing, modular rooms offering high performance and aesthetic appeal.  Our Rigidwall system is perfect for pharmacies that are required to meet ISO Class 7 for USP 797.  Our Rigidwall cleanrooms utilize adjustable louvers to achieve correct pressure relationships between rooms.

Panels are available in three types:

Acrylic Panels

Acrylic panels offer the best scratch resistance and overall value. Standard Panels are clear, but black and opaque are available.

Static Dissipative PVC Panels

Static dissipative PVC panels are recommended where static charges must be kept to a minimum. These panels also resist attraction of particulate.

Polycarbonate Panels

Polycarbonate panels offer superior impact resistance and are better for environments where acids and solvents will be used.

Available Sizes Standard Rooms available in 2’x4’ increments. Custom sizes also available. Clearspans up to 30′.
Room Class ISO Class 8 (100,000) to ISO Class 4 (10).
Frame Construction High-strength 6063-T6 Extruded Aluminum.
Finish White Powder-baked Enamel.
Filtration Standard model 421-SPX motorized HEPA fan filter units, 99.99% efficient at MPPS. Several sizes and options available, including advanced automation and monitoring.
Walls 1/4” Clear Acrylic in powder-coated extruded aluminum frames. Standard frames are 4’x 8’h – up to 16’h. Clear Polycarbonate, and white Polypropylene, as well as Antistatic Acrylic or Polycarbonate are also available.
Entries Doors can be hinged, sliding or strips. Hinged doors have hydraulic closers, heavy duty stainless steel hinges and aluminum pull handles. Panic hardware also available.
Lighting 2’x 4′ standard light troffers with (4) F32-T8 tubes. Several sizes and options available, including LED and Flow Through lights.
Blank Panels 1/2” gypsum, vinyl faced on both sides with sealed edges.
Electrical Filters are standard with a variable speed control and 8′ power cord. Light fixtures have ballast wires inside a top-mounted access cover for connection.
Voltage Standard voltage for filters is 120/1/60, with options available of 220/1/50-60 and 277/1/60. Lights are Universal 120-277/1/60. Panels over 30 amps at 120V can also be factory wired to accept 220/1/60 input at no extra charge.
Optional Prewiring Rooms can come with components factory wired with “plug and play” connections to a central control panel. The panel is a powder-coated NEMA 1 enclosure with face-mounted variable speed controls and light switches. A power distribution block is also provided for connection to field power.
  • Modular rooms available from Class 10-10,000 (ISO 4-8)
  • Fabricated aluminum extrusion wall panels that are finished with white powder baked enamel to prevent contamination.
  • Standard 4’x 8′ panel size for modular expansion and configuration.
  • Gown rooms added internally or externally.
  • Expandable as your business requirements change.
  • Cost Savings of 25-30% over tranditional sheet rock or construction cleanrooms.

Any rating from Class 10-10,000

Our HEPA filters are included with your cleanroom, so we can guarantee the room will meet the class you require from Class 10-10,000. Our filter units offer an exceptional level of performance and value in a quiet package.

Meets USP 797

Our rigidwall cleanrooms are perfect for pharmacies required to meet ISO Class 7 for USP 797. Rooms are installed on the floor with adjustable louvers to achieve the correct pressure relationships between cleanrooms and ante rooms.

To monitor the pressure, we utilize magnehelic gauges mounted to a wall for easy viewing. For chemo rooms, we utilize exhaust pressure to the ante room, with another gauge added.

Design Expertise

For over 25 years, Technical Air Products has been designing high-quality clean air products.  Our engineers can assist you in designing a cleanroom, or cleanroom components to meet your exact needs.  CAD drawings will be created for your specific requirements, so no details will be missed.  Contact us today, and let our design experts go to work for you.

Call us Toll-Free:  800-595-0020